SIL Study means performing SIL assessment, preparing a SRS (Safety Requirements Specification) report and performing SIL verification activities in order to check SIL (Safety Integrity Level) status of the target device or product. SIL Study method uses LOPA (Layer of Protection Analysis) method and QRA (Quantitative Risk Analysis) method.
SIS ID : |
SIS-x-L0XXX |
Service : xxxx Compressor Suction Scrubber LL level with Gas blow-by to drain seal drum and potential damage to drum |
||||
---|---|---|---|---|---|---|
TAG # : |
0x-LLT-XXX |
|||||
Required SIL : |
SIL 1 |
|||||
Demand rate on SIS : |
Low demand |
|||||
Test interval : |
1 year (to be confirmed by SIL verification) |
|||||
Response Time : |
Refer to general Requirements |
|||||
Method : |
De-energize to trip |
Safe state : Emergency Shutdown Valve (ESDV xxxx) between compressor suction scrubber and drain seal drum closed |
||||
Reset Type : |
Refer to general Requirements |
|||||
Nuisance Trip Req’s : |
Refer to general Requirements |
|||||
Special Diagnostics |
Transmitter usual diagnostic by PLC |
|||||
Manual Shutdown |
Existing (manual control of ESDV xxxx) |
|||||
Regulatory Req : |
Refer to general Requirements |
|||||
MTTR : |
4 hours expected |
|||||
Cause & Effect Diagram
|
EFFECT |
DESCRIPTION |
Close shutdown valve to drain drum |
|||
cause |
TAG |
07-ESDV-100 |
||||
Tag |
Description |
Alarm Tag |
Trip Point |
Notes |
||
15-L010 |
Suction scrubber Low Low level |
15-AT-020 |
To be defined |
X |
SIL | Low demand mode of operation(Average probability of failure to perform its design function on demand PFD) | High demand or continuous mode of operation(Probability of a dangerous failure per hour PFH) |
---|---|---|
1 | 10-2 < PFD < 10-1 | 10-6 < PFH < 10-5 |
2 | 10-3 < PFD < 10-2 | 10-7 < PFH < 10-6 |
3 | 10-4 < PFD < 10-3 | 10-8 < PFH < 10-7 |
4 | 10-5 < PFD < 10-4 | 10-9 < PFH < 10-8 |